Aux Commercial Floor Standing AC Error Codes

The fault The fault Code definition Possible cause Solution
Code
1. The outdoor unit is the power off 1. Turn on the power for the outdoor unit
Communication the fault 2. The communication wire of units lost 2. Reconnect firmly
F1 3. Insert the wrong plug into the indoor or outdoor unit control board 3. Loosen and insert the right plug
between the indoor unit and
4. The communication wire is an open or short circuit 4. Replace a normal communication wire
the outdoor unit
5. The indoor unit control board malfunction 5. Replace the control board
6. The outdoor unit control board malfunction 6. Replace the control board
Input the power supply phase 1. Phase loss 1. Reconnect the wires firmly
E6 2. Low-voltage 2. Check if the power supply is consistent with the
sequence protection
3. Phase dislocation nameplate
(The outdoor unit)
3. Exchange the two-phase sequence of the power supply
1. Sensor directly contacts with the heat exchanger 1. Refix the sensor correctly
E1 The indoor ambient temperature 2. Sensor plug insert again 2. Reinsert
sensor the fault 3. Sensor is an open or short circuit 3. Replace the sensor
4. The indoor unit control board malfunction 4. Replace the indoor unit control board
F3 the outdoor fan protection 1. The outdoor unit ventilation is insufficient 1. Improve or enhance the ventilation
2. The fan motor stuck 2. Replace the fan motor
1. the outdoor fan blade is broken 1. Replace the fan blade
2. the connection between the fan blade and the outdoor fan motor 2. Tighten or replace the sleeve
loose
3. the outdoor fan stops working 3. Eliminate the malfunction cause
F2 Discharge temperature 4. the outdoor ventilation is insufficient 4. Improve or enhance the ventilation
protection 5. the outdoor exchanger is dirty or sticky 5. Clean the heat exchanger
6. discharge temperature sensor deviation 6. Replace the sensor
7. Refrigerant leak 7. Find out the leak point, repair the welding, refill the freon unit
after vacuuming it
8. The capillary or the filter is blocked 8. Replace the capillary or filter
1. the globe valve is closed 1. Open the globe valve
2. the outdoor fan blade is broken 2. Replace the fan blade
3. the connection between the fan blade and the outdoor fan motor 3. tighten or replace the sleeve
EH High-pressure protection loose
4. the outdoor fan stops working 4. Eliminate the malfunction cause
5. the outdoor ventilation is insufficient 5. Improve or enhance the ventilation
6. the connection between the high-pressure switch and the control board 6. Reconnect the wire to the control board
loose

 

7. High-pressure switch malfunction 7. Replace the high-pressure switch
8. the outdoor exchanger is dirty or sticky 8. Clean the heat exchanger
9. there are some moistures in the refrigerant line 9. Refill the freon unit after vacuuming it
10. The capillary or the filter is blocked 10. Replace the capillary or filter
1. the globe valve is closed 1. open the globe valve
2. the indoor fan blade is broken 2. tighten or replace the sleeve
3. the connection between the fan blade and the indoor fan motor 3. the indoor fan blade was broken
loose
4. the outdoor fan stops working 4. Eliminate the malfunction cause
EL Low-pressure protection 5. The filter net is dirty 5. Clean the filter
6. Refrigerant leak 6. Find out the leak point, repair the welding, refill the freon unit
after vacuuming it
7. the connection between the low-pressure switch and the control board 7. Reconnect the wire to the control board
loose
8. Low-pressure switch malfunction 8. Replace the low-pressure switch
9. The capillary or the filter is blocked 9. Replace the capillary or filter
1. Refrigerant leak 1. Find out the leak point, repair the welding, refill the freon
E0 Refrigerant lack protection/4- unit after vacuuming it
2. 4-way valve coil open or short circuit 2. Replace the 4-way valve coil
way valve the fault protection
3. Valve block cannot get the designated position or Valve blow- 3. Replace the 4-way valve
by
1. Sensor separates from the coil 1. Refix the sensor correctly
E3 The indoor coil temperature sensor 2. Sensor plug insert again 2. Reinsert
the fault (TE) 3. Sensor is an open or short circuit 3. Replace the sensor
4. The indoor unit control board malfunction 4. Replace the indoor unit control board
1. Sensor separates from the coil 1. Refix the sensor correctly
E2 The outdoor coil temperature sensor 2. Sensor plug insert again 2. Reinsert
the fault (TW) 3. Sensor is an open or short circuit 3. Replace the sensor
4. The outdoor unit control board malfunction 4. Replace the outdoor unit control board
1. The sensor separate from the copper tube 1. Refix the sensor correctly
E8 Discharge temperature (TP) 2. Sensor plug insert again 2. Reinsert
sensor the fault 3. Sensor is an open or short circuit 3. Replace the sensor
4. The outdoor unit control board malfunction 4. Replace the outdoor unit control board
E9 Electric heating protection 1. An electric heater is an open or short-circuit 1.  Replace a normal one
2.  The blower malfunction 2.  Replace a normal one

 

Leave a Comment