Aux Duct Type AC Error Codes

The fault The fault code definition Possible cause Solution
code
1.  The connection loose 1.  reconnect firmly
E5 Wired controller 2.  Wired controller malfunction 2.  replace a new one
3.  The communication wire is an open or short circuit 3.  replace normal 
communication with the fault
4.  The indoor unit control board malfunction 4. replace a new one
1. The drain pipe is blocked 1.  Clean the drain pipe
E4 2.  Float switch short-circuit or unconnected 2.  Rapace float switch or reconnect it
Drainage system the fault 3.  The power line of the water pump lose 3.  Reconnect the power line of the water pump
4.  The water pump is broken 4. Replace the water pump
5. The indoor PCB is broken 5. Replace PCB
1. Sensor directly contacts with the heat exchanger 1. Refix the sensor correctly
E1 The indoor ambient temperature 2. Sensor plug insert again 2. Reinsert
sensor the fault 3. Sensor is an open or short circuit 3. Replace the sensor
4. The indoor unit control board malfunction 4. Replace the indoor unit control board
1. Sensor separated from the coil 1. Refix the sensor correctly
E3 The indoor coil temperature sensor 2. Sensor plug insert again 2. Reinsert
the fault (TE) 3. Sensor is an open or short circuit 3. Replace the sensor
4. The indoor unit control board malfunction 4. Replace the indoor unit control board
1. Sensor separated from the coil 1. Refix the sensor correctly
E2 The outdoor coil temperature sensor 2. Sensor plug insert again 2. Reinsert
the fault (TW) 3. Sensor is an open or short circuit 3. Replace the sensor
4. The outdoor unit control board malfunction 4. Replace the outdoor unit control board
1. Sensor directly contacts with the heat exchanger 1. Refix the sensor correctly
E7 The outdoor ambient temperature 2. Sensor plug insert again 2. Reinsert
the sensor with the fault (TL) 3. Sensor is an open or short circuit 3. Replace the sensor
4. The outdoor unit control board malfunction 4. Replace the outdoor unit control board
1. Refrigerant leak 1. Find out the leak point, repair the welding, refill
E0 Refrigerant lack protection/4-way the unit after vacuuming it
valve the fault protection 2. 4-way valve coil open or short circuit 2. Replace the 4-way valve coil
3. Valve block cannot get the designated position or Valve blow-by 3. Replace the 4-way valve

 

1. The outdoor unit is the power off 1. Turn on the power for the outdoor unit
Communication the fault 2. The communication wire of units lost 2. Reconnect firmly
F1 3. Insert the wrong plug into the indoor or outdoor unit control board 3. Loosen and insert the right plug
between the indoor unit and
the outdoor unit 4. The communication wire is an open or short circuit 4. Replace a normal communication wire
5. The indoor unit control board malfunction 5. Replace the control board
6. The outdoor unit control board malfunction 6. Replace the control board
1. The connection loose 1. Reconnect firmly
E5 Wired controller 2. Wired controller malfunction 2. Replace a new one
communication the fault 3. The communication wire is an open or short circuit 3. Replace a normal one
4. The indoor unit control board malfunction 4. Replace a new one
1. The drain pipe is blocked 1. Clean the drain pipe
E4 2. Float switch short-circuit or unconnected 2. Repace the float switch or reconnect it
Drainage system the fault 3. The power line of the water pump loose 3. Reconnect the power line of the water pump
4. The water pump is broken 4. Replace the water pump
5. The indoor PCB is broken 5. Replace PCB
Input the power supply phase 1. Phase loss 1. Reconnect the wires firmly
E6 2. Low-voltage 2. Check if the power supply is consistent with the
sequence protection nameplate
(The outdoor unit) 3. Phase dislocation 3. Exchange the two-phase sequence of the power
supply
1. the outdoor fan blade broken 1. Replace the fan blade
2. the connection between the fan blade and the outdoor fan motor 2. Tighten or replace the sleeve
loose
3. the outdoor fan stops working 3. Eliminate the malfunction cause
EA Discharge temperature 4. the outdoor ventilation insufficient 4. Improve or enhance the ventilation
protection 5. the outdoor exchanger is dirty or sticky 5. Clean the heat exchanger
6. discharge temperature sensor deviation 6. Replace the sensor
7. Refrigerant leak 7. Find out the leak point, repair the welding, refill the freon
unit after vacuuming it
8. The capillary or the filter is blocked 8. Replace the capillary or filter
E9 High-pressure protection 1. the globe valve is closed 1. Open the globe valve
2. the outdoor fan blade broken 2. Replace the fan blade

 

3. the connection between the fan blade and the outdoor fan motor 3. tighten or replace the sleeve
loose
4. the outdoor fan stops working 4. Eliminate the malfunction cause
5. the outdoor ventilation insufficient 5. Improve or enhance the ventilation
6. the connection between the high-pressure switch and the control 6. Reconnect the wire to the control board
board lose
7. High-pressure switch malfunction 7. Replace the high-pressure switch
8. the outdoor exchanger is dirty or sticky 8. Clean the heat exchanger
9. there are some moistures in the refrigerant line 9. Refill the freon unit after vacuuming it
10. The capillary or the filter is blocked 10. Replace the capillary or filter
1. The globe valve is closed 1. Open the globe valve
2. The indoor fan blade broken 2. Tighten or replace the sleeve
3. The connection between the fan blade and the indoor fan motor 3. The indoor fan blade broken
loose
4. The outdoor fan stops working 4. Eliminate the malfunction cause
E9 Low-pressure protection 5. Filter net is dirty 5. Clean the filter
6. Refrigerant leak 6. Find out the leak point, repair the welding, refill the freon
unit after vacuuming it
7. The connection between the low-pressure switch and the control 7. Reconnect the wire to the control board
board lose
8. Low-pressure switch malfunction 8. Replace the low-pressure switch
9. The capillary or the filter is blocked 9. Replace the capillary or filter
1. Sensor directly contacts with the heat exchanger 1. Refix the sensor correctly
E1 The indoor ambient temperature 2. Sensor plug insert again 2. Reinsert
sensor the fault 3. Sensor is an open or short circuit 3. Replace the sensor
4. The indoor unit control board malfunction 4. Replace the indoor unit control board
1. Sensor separated from the coil 1. Refix the sensor correctly
E3 The indoor coil temperature sensor 2. Sensor plug insert again 2. Reinsert
the fault (TE) 3. Sensor is an open or short circuit 3. Replace the sensor
4. The indoor unit control board malfunction 4. Replace the indoor unit control board
1. Sensor separated from the coil 1. Refix the sensor correctly
E2 The outdoor coil temperature 2. Sensor plug insert again 2. Reinsert
sensor the fault (TW) 3. Sensor is an open or short circuit 3. Replace the sensor
4. The outdoor unit control board malfunction 4. Replace the outdoor unit control board
The outdoor ambient 1. Sensor directly contacts with the heat exchanger 1. Refix the sensor correctly
E7 2. Sensor plug insert again 2. Reinsert
temperature. Sensor
3. Sensor is an open or short circuit 3. Replace the sensor
abnormal (TL)
4. the outdoor unit control board malfunction 4. Replace the outdoor unit control board
E8 Discharge temperature 1. The sensor separated from the copper tube 1. Refix the sensor correctly
(Spenser the fault 2. Sensor plug insert again 2. Reinsert

 

3. Sensor is an open or short circuit 3. Replace the sensor
4. The outdoor unit control board malfunction 4. Replace the outdoor unit control board
1. Refrigerant leak 1. Find out the leak point, repair the welding, refill the freon
E11 Refrigerant lack protection/4- unit after vacuuming it
2. 4-way valve coil open or short circuit 2. Replace the 4-way valve coil
way valve the fault protection
3. Valve block cannot get the designated position or Valve blow- 3. Replace the 4-way valve
by

 

Leave a Comment