Aux King Kong type Chiller AC Error Codes

Models: ACMK-H65/5, ACMK-H130/5

The fault The fault code definition possible cause Solution
code
1. The water flow switch and the power supply wires are not well connected 1. reconnect the wires firmly
2. The water flow switch malfunction 2. Replace a normal water flow switch
E01 The water flow switch protection 3. Circulating the water pump malfunction 3. Repair or replace the circulating water pump
4. The water filter clogging 4. Clean or replace the water filter
5. The evaporator tubes have a dirty plugging phenomenon 5. Clean the evaporator tubes
E05 The power supply phase sequence 1. Phase loss 1. reconnect the wires firmly
protection 2. Phase dislocation 2. change the two-phase sequence of the power supply
Return the water temperature 1. The temperature sensor broken 1. Replace the sensor
E07 2. Sensor plug insert again to PCB 2. Reconnect the sensor firmly
sensor the fault
3. Main control board malfunction 3. Replace the main control board
The water outlet temperature sensor 1. The temperature sensor broken 1. Replace the sensor
E08 2. Sensor plug insert again to PCB 2. Reconnect the sensor firmly
the fault
3. Main control board malfunction 3. Replace the main control board
The outdoor   ambient   temperature 1. The temperature sensor broken 1. Replace the sensor
E09 2. Sensor plug insert again to PCB 2. Reconnect the sensor firmly
sensor the fault 3. Main control board malfunction 3. Replace the main control board
1. The temperature sensor broken 1.  Replace the temperature sensor
E12 Anti-hyperthermal protection 2. Circulating the water pump malfunction 2. Repair or replace the circulating water pump
in heating mode 3. The water filter clogging 3.  Clean or replace the water filter
4. The evaporator tubes have a dirty plugging phenomenon 4. Clean the evaporator tubes
The water flow shortage protection 1. The return of the water temperature or the water inlet sensor broken 1.  Replace the temperature sensor
2. The water filter clogging 2. Clean or replace the water filter
E13 (Chilled the water big temperature
3. Circulating the water pump malfunction 3.  Repair or replace the circulating water pump
difference)
4. The evaporator tubes have a dirty plugging phenomenon 4. Clean the evaporator tubes
1. The connection plug loose 1. reconnect firmly
E15 Communication the fault between 2. Wired controller malfunction 2. replace a new one
wired controller and PCB 3. The communication wire is an open or short circuit 3. replace a normal one
4. Main control board malfunction 4. replace a new one
1. The connection plug loose 1. reconnect firmly
Communication the fault between 2. The communication wire between modules is a short circuit 2. replace a new one
E30 or open circuit
different modules
3. The communication wire is an open or short circuit 3. replace a normal one
4. Main control board malfunction 4. replace a new one

 

E18 Subsystem1#highpressure 1. the outdoor ventilation is insufficient 1. Improve or enhance the ventilation
protection 2. the outdoor fan blade is broken 2. Replace the fan blade
3. the connection between the fan blade and the outdoor fan 3. Tighten or replace the sleeve
E19 Subsystem 2#high pressure motor lose
protection 4. the outdoor fan stops working 4. Eliminate the malfunction cause
5. the connection between the high-pressure switch and the main 5. Reconnect the wire plug to the main control board
Subsystem 3#high pressure
E20 control board lose
protection 6. High-pressure switch malfunction 6. Replace the high-pressure switch
7. the outdoor exchanger is dirty or sticky 7. Clean the heat exchanger
Subsystem 4#high pressure
E21 8. there are some airs in the refrigerant line 8. Refill the freon unit after vacuuming it
protection 9. The capillary or the filter is blocked 9. Replace the capillary or filter
E22 Subsystem 1#low pressure 1. Circulating the water pump malfunction 1. Repair it or change a normal one
2. Clean the water filter
protection 2. The water filter clogging
3. Clean the evaporator tubes
E23 Subsystem 2#low pressure 3. The evaporator tubes have a dirty plugging phenomenon
4. The connection between the low-pressure switch and the main
protection 4. Reconnect the wire to the main control board
control board lose
Subsystem 3#low pressure
E24 5. Low-pressure switch malfunction 5. Replace the low-pressure switch
protection 6. Refrigerant leak
6. Find out the leak point, repair the welding, refill the freon unit
Subsystem 4#low pressure
E25 7. The capillary or the filter is blocked after vacuuming it
protection
7. Replace the capillary or filter
Subsystem 1# air discharge 1. the outdoor ventilation is insufficient 1. Improve or enhance the ventilation
2. the outdoor fan blade is broken 2. Replace the fan blade
E26 temperature overhigh
protection 3. the connection between the fan blade and the outdoor fan 3. Tighten or replace the sleeve
motor lose
Subsystem 2# air discharge
E27 4. the outdoor fan stops working 4. Eliminate the malfunction cause
temperature overhigh 5. the connection between the discharge temperature sensor 5. Reconnect the wire plug to the main control board
protection
and the main control board lose
Subsystem 3# air discharge 6. the outdoor exchanger is dirty or sticky 6. Clean the heat exchanger
7. discharge temperature sensor deviation 7. Replace the sensor
E28 temperature overhigh
8. Refrigerant leak 8. Find out the leak point, repair the welding, refill the freon unit
protection
after vacuuming it
Subsystem 4# air discharge 9. The indoor capillary or the filter is blocked
9. Replace the capillary or filter
E29 temperature overhigh 10. there are some airs in the refrigerant line 10. Find out the leak point, repair the welding, refill the freon
protection unit after vacuuming it
1. the water outlet temperature sensor malfunction 1. Replace a normal one
2. Circulating the water pump malfunction 2. Repair it or change a normal one
E33 Anti-freezing protection in 3. The water filter clogging 3. Clean the water filter
cooling mode 4. The evaporator tubes have a dirty plugging phenomenon 4. Clean the evaporator tubes
5. Refrigerant leak 5. Find out the leak point, repair the welding, refill the freon unit
after vacuuming it

 

E34 Subsystem 1# the compressor 1. The outdoor ventilation is insufficient 1. Improve or enhance the ventilation
overcurrent protection 2. Tighten or replace the sleeve
2. The connection between the fan blade and the outdoor fan
Subsystem 2# the compressor
E35 motor lose 3. Eliminate the malfunction cause
overcurrent protection 3. the outdoor fan stops working
4. Replace the fan blade
4. The outdoor fan blade is broken
Subsystem 3# the compressor
E36 5. Clean the heat exchanger
5. The outdoor exchanger is dirty or sticky
overcurrent protection 6. Replace the capillary or filter
6. Pipeline ice blocking or dirty
Subsystem 4# the compressor 7. Release some refrigerant
E37 7. Refrigerant overcharged
overcurrent protection
E38 Subsystem 1# 4-way valve the fault 1. 4-way valve coil open or short circuit 1. Replace valve coil
2. Valve block cannot get the designated position or Valve 2. Replace valve body
E39 Subsystem 2# 4-way valve the fault
blow-by
E40 Subsystem 3# 4-way valve the fault 3. The outdoor ambient temperature sensor or exchanger coil 3. Replace a normal one
temperature sensor malfunction
E41 Subsystem 4# 4-way valve the fault
4. The main PCB failure 4. Replace the main PCB board
E42 Subsystem 1# discharge
temperature sensor the fault
E43 Subsystem 2# discharge 1. Sensor is an open or short circuit 1. Replace the sensor
temperature sensor the fault
2. Sensor plug insert again 2. Reinsert firmly
Subsystem 3# discharge
E44 3. Main control board malfunction 3. Replace the main control board
temperature sensor the fault
E45 Subsystem 4# discharge
temperature sensor the fault
E46 Subsystem 1# exchanger coil
temperature sensor the fault
E47 Subsystem 2# exchanger coil 1. Sensor is an open or short circuit 1. Replace the sensor
temperature sensor the fault
2. Sensor plug insert again 2. Reinsert firmly
Subsystem 3# exchanger coil
E48 3. Main control board malfunction 3. Replace the main control board
temperature sensor the fault
E49 Subsystem 4# exchanger coil
temperature sensor the fault
E53 Module type dip switch setting Module type dip switch setting incorrect Reset the Module type dip switch setting concerning the
incorrect wiring diagram
E54 Module address repeat Module address dip switch setting incorrect reset address setting dip switch concerning wiring
diagram as needed

 

 