Models: ACMI-H12/4, ACMI-H16/5, ACMI-H28/5, ACMI-H42/5
The fault | The fault code definition | Possible cause | solution | |||
code | ||||||
1. The connection plug loose | 1. Reconnect firmly | |||||
Eon | : | 00 | Communication the fault | 2. The communication wire is an open or short circuit | 2. Replace a normal one | |
3. Main control board malfunction | 3. Replace a new one | |||||
1 、 The water flow switch and the power supply wires are not well | 1. reconnect the wires firmly | |||||
connected | ||||||
Eon | : | 01 | The water flow switch protection | 2. The water flow switch malfunction | 2. Replace a normal water flow switch | |
3. Circulating the water pump malfunction | 3. Repair or replace the circulating water pump | |||||
4. The water filter clogging | 4. Clean or replace the water filter | |||||
5. The evaporator tubes have a dirty plugging phenomenon | 5. Clean the evaporator tubes | |||||
Eo:02 | The outdoor fan motor overload | 1. The outdoor unit ventilation is insufficient | 1. Improve or enhance the ventilation | |||
2. The fan motor stuck | 2. Replace the fan motor | |||||
Eo:03 | Input the power supply phase sequence | 1. Phase loss | 1. reconnect the wires firmly | |||
protection | 2. Phase dislocation | 2. change the two-phase sequence of the power supply | ||||
1 The return of the water temperature or the water inlet sensor | 1. Replace the temperature sensor | |||||
The water flow shortage protection | broken | 2. Clean or replace the water filter | ||||
Eo:04 | 2. The water filter clogging | 3. Repair or replace the circulating water pump | ||||
(Chilled the water big temperature difference) | ||||||
3. Circulating the water pump malfunction | 4. Clean the evaporator tubes | |||||
4. The evaporator tubes have a dirty plugging phenomenon | ||||||
Eo:06 | Freezing point protection switch | The freezing point protection switch is off | Press the reset key to reset | |||
1. The temperature sensor broken | 1. Replace the temperature sensor | |||||
Eo:07 | Anti-hyperthermal protection | 2. Circulating the water pump malfunction | 2. Repair or replace the circulating water pump | |||
in heating mode | 3. The water filter clogging | 3. Clean or replace the water filter | ||||
4. The evaporator tubes have a dirty plugging phenomenon | 4. Clean the evaporator tubes | |||||
High discharge temperature protection of | 1. The outdoor ventilation is insufficient | 1. Improve or enhance the ventilation | ||||
Er:03 | 2. The outdoor fan blade is broken | 2. Replace the fan blade | ||||
subsystem 1# | 3. The connection between the fan blade and the outdoor fan | 3. Tighten or replace the sleeve | ||||
motor lose | ||||||
4. The outdoor fan stops working | 4. Eliminate the malfunction cause | |||||
5 、 The connection between discharge temperature | 5. Reconnect the wire plug to the main control board | |||||
sensor and main control board lose | ||||||
High discharge temperature protection of | 6. The outdoor exchanger is dirty or sticky | 6. Clean the heat exchanger | ||||
Er:13 | 7. Discharge temperature sensor deviation | 7. Replace the sensor | ||||
subsystem 2# | 8. Refrigerant leak | 8. Find out the leak point, repair the welding, refill | ||||
the unit after vacuuming it | ||||||
9. The indoor capillary or the filter is blocked | 9. Replace the capillary or filter | |||||
10. There are some airs in the refrigerant line | 10. Find out the leak point, repair the welding, refill | |||||
the unit after vacuuming it | ||||||
1. The outdoor ventilation is insufficient | 1. Improve or enhance the ventilation | |||||
2. The outdoor fan blade is broken | 2. Replace the fan blade | |||||
High-pressure protection of subsystem 1# | 3. The connection between the fan blade and the outdoor fan | 3. Tighten or replace the sleeve | ||||
: | motor lose | |||||
Er 04 | ||||||
4. The outdoor fan stops working | 4. Eliminate the malfunction cause | |||||
5. The connection between the high-pressure switch and | 5. Reconnect the wire plug to the main control board | |||||
main control board lose | ||||||
6. High-pressure switch malfunction | 6. Replace the high-pressure switch | |||||
Er:14 | High-pressure protection of subsystem 2# | 7. The outdoor exchanger is dirty or sticky | 7. Clean the heat exchanger | |||
8. There are some airs in the refrigerant line | 8. Refill the freon unit after vacuuming it | |||||
9. The capillary or the filter is blocked | 9. Replace the capillary or filter | |||||
1. Circulating the water pump malfunction | 1. Repair it or change a normal one | |||||
Er:05 | low suction pressure protection of | 2. The water filter clogging | 2. Clean the water filter | |||
Subsystem 1# | 3. The evaporator tubes have a dirty plugging phenomenon | 3. Clean the evaporator tubes | ||||
4. The connection between the low-pressure switch and the main | 4. Reconnect the wire to the main control board | |||||
control board lose | ||||||
low suction pressure protection of | 5. Low-pressure switch malfunction | 5. Replace the low-pressure switch | ||||
Er:15 | 6. Refrigerant leak | 6. Find out the leak point, repair the welding, refill | ||||
Subsystem 2# | the unit after vacuuming it | |||||
7. The capillary or the filter is blocked | 7. Replace the capillary or filter | |||||
1. The temperature sensor broken | 1. Replace the sensor | |||||
: | 01 | Return the water temperature to the fault | 2. Sensor plug insert again to PCB | 2. Reconnect the sensor firmly | ||
Po | 3. Main control board malfunction | 3. Replace the main control board | ||||
The outdoor ambient temperature sensor | 1. The temperature sensor broken | 1. Replace the sensor | ||||
: | 02 | 2. Sensor plug insert again to PCB | 2. Reconnect the sensor firmly | |||
Po | the fault | 3. Main control board malfunction | 3. Replace the main control board | |||
1. The water outlet temperature sensor malfunction | 1. Replace a normal one | ||||
2. Repair it or change a normal one | |||||
2. Circulating the water pump malfunction | |||||
3. Clean the water filter | |||||
: | 03 | Anti-freezing protection in cooling mode | 3. The water filter clogging | ||
Po | 4. The evaporator tubes have a dirty plugging phenomenon | 4. Clean the evaporator tubes | |||
5. Refrigerant leak | 5. Find out the leak point, repair the welding, refill | ||||
the unit after vacuuming it | |||||
1. The temperature sensor broken | 1. Replace the sensor | ||||
: | 06 | The water outlet temperature is the fault | 2. Sensor plug insert again to PCB | 2. Reconnect the sensor firmly | |
Po | 3. Main control board malfunction | 3. Replace the main control board | |||
: | 07 | Circulating the water anti-freezing protection in | The outdoor ambient temperature is too low | Start the heating mode | |
Po | winter | ||||
Pr:02 | Exchanger coil temperature sensor the fault of | 1. Sensor is an open or short circuit | 1. Replace the sensor | ||
subsystem 1# | 2. Sensor separated from the copper tube | 2. Refix the sensor correctly | |||
Pr:12 | Exchanger coil temperature sensor the fault of | 3. Sensor plug insert again | 3. Reinsert firmly | ||
subsystem 2# | 4. Main control board malfunction | 4. Replace the main control board | |||
Pr:03 | Discharge temperature sensor the fault of | 1. Sensor is an open or short circuit | 1. Replace the sensor | ||
subsystem 1# | 2. The sensor separates from the copper tube | 2. Refix the sensor correctly | |||
Pr:13 | Discharge temperature sensor the fault of | 3. Sensor plug insert again | 3. Reinsert firmly | ||
4. Main control board malfunction | 4. Replace the main control board | ||||
subsystem 2# | |||||
1. The outdoor ventilation is insufficient | 1. Improve or enhance the ventilation | ||||
Pr:04 | Cooling overload protection of subsystem | 2. The outdoor fan blade is broken | 2. Replace the fan blade | ||
1# | 3. The connection between the fan blade and the outdoor fan | 3. Tighten or replace the sleeve | |||
motor lose | |||||
4. The outdoor fan stops working | 4. Eliminate the malfunction cause | ||||
5. Exchanger coil bottom temperature sensor malfunction | 5. Replace the sensor | ||||
Pr:14 | Cooling overload protection of subsystem | 6. The outdoor exchanger is dirty or sticky | 6. Clean the heat exchanger | ||
2# | 7. There are some airs in the refrigerant line | 7. Refill the freon unit after vacuuming it | |||
8. The capillary or the filter is blocked | 8. Replace the capillary or filter | ||||