Aux Mini Chiller AC Error Codes

Models: ACMI-H12/4, ACMI-H16/5, ACMI-H28/5, ACMI-H42/5

The fault The fault code definition Possible cause solution
code
1. The connection plug loose 1. Reconnect firmly
Eon 00 Communication the fault 2. The communication wire is an open or short circuit 2. Replace a normal one
3. Main control board malfunction 3. Replace a new one
1 、 The water flow switch and the power supply wires are not well 1. reconnect the wires firmly
connected
Eon 01 The water flow switch protection 2. The water flow switch malfunction 2. Replace a normal water flow switch
3. Circulating the water pump malfunction 3. Repair or replace the circulating water pump
4. The water filter clogging 4. Clean or replace the water filter
5. The evaporator tubes have a dirty plugging phenomenon 5. Clean the evaporator tubes
Eo:02 The outdoor fan motor overload 1. The outdoor unit ventilation is insufficient 1. Improve or enhance the ventilation
2. The fan motor stuck 2. Replace the fan motor
Eo:03 Input the power supply phase sequence 1. Phase loss 1. reconnect the wires firmly
protection 2. Phase dislocation 2. change the two-phase sequence of the power supply
1 The return of the water temperature or the water inlet sensor 1.  Replace the temperature sensor
The water flow shortage protection broken 2. Clean or replace the water filter
Eo:04 2. The water filter clogging 3.  Repair or replace the circulating water pump
(Chilled the water big temperature difference)
3. Circulating the water pump malfunction 4. Clean the evaporator tubes
4. The evaporator tubes have a dirty plugging phenomenon
Eo:06 Freezing point protection switch The freezing point protection switch is off Press the reset key to reset
1. The temperature sensor broken 1.  Replace the temperature sensor
Eo:07 Anti-hyperthermal protection 2. Circulating the water pump malfunction 2. Repair or replace the circulating water pump
in heating mode 3. The water filter clogging 3.  Clean or replace the water filter
4. The evaporator tubes have a dirty plugging phenomenon 4. Clean the evaporator tubes
High discharge temperature protection of 1. The outdoor ventilation is insufficient 1. Improve or enhance the ventilation
Er:03 2. The outdoor fan blade is broken 2. Replace the fan blade
subsystem 1# 3. The connection between the fan blade and the outdoor fan 3. Tighten or replace the sleeve
motor lose

 

4. The outdoor fan stops working 4. Eliminate the malfunction cause
5 、 The connection between discharge temperature 5. Reconnect the wire plug to the main control board
sensor and main control board lose
High discharge temperature protection of 6. The outdoor exchanger is dirty or sticky 6. Clean the heat exchanger
Er:13 7. Discharge temperature sensor deviation 7. Replace the sensor
subsystem 2# 8. Refrigerant leak 8. Find out the leak point, repair the welding, refill
the unit after vacuuming it
9. The indoor capillary or the filter is blocked 9. Replace the capillary or filter
10. There are some airs in the refrigerant line 10. Find out the leak point, repair the welding, refill
the unit after vacuuming it
1. The outdoor ventilation is insufficient 1. Improve or enhance the ventilation
2. The outdoor fan blade is broken 2. Replace the fan blade
High-pressure protection of subsystem 1# 3. The connection between the fan blade and the outdoor fan 3. Tighten or replace the sleeve
motor lose
Er 04
4. The outdoor fan stops working 4. Eliminate the malfunction cause
5. The connection between the high-pressure switch and 5. Reconnect the wire plug to the main control board
main control board lose
6. High-pressure switch malfunction 6. Replace the high-pressure switch
Er:14 High-pressure protection of subsystem 2# 7. The outdoor exchanger is dirty or sticky 7. Clean the heat exchanger
8. There are some airs in the refrigerant line 8. Refill the freon unit after vacuuming it
9. The capillary or the filter is blocked 9. Replace the capillary or filter
1. Circulating the water pump malfunction 1. Repair it or change a normal one
Er:05 low suction pressure protection of 2. The water filter clogging 2. Clean the water filter
Subsystem 1# 3. The evaporator tubes have a dirty plugging phenomenon 3. Clean the evaporator tubes
4. The connection between the low-pressure switch and the main 4. Reconnect the wire to the main control board
control board lose
low suction pressure protection of 5. Low-pressure switch malfunction 5. Replace the low-pressure switch
Er:15 6. Refrigerant leak 6. Find out the leak point, repair the welding, refill
Subsystem 2# the unit after vacuuming it
7. The capillary or the filter is blocked 7. Replace the capillary or filter
1. The temperature sensor broken 1. Replace the sensor
01 Return the water temperature to the fault 2. Sensor plug insert again to PCB 2. Reconnect the sensor firmly
Po 3. Main control board malfunction 3. Replace the main control board
The outdoor ambient temperature sensor 1. The temperature sensor broken 1. Replace the sensor
02 2. Sensor plug insert again to PCB 2. Reconnect the sensor firmly
Po the fault 3. Main control board malfunction 3. Replace the main control board

 

 

1. The water outlet temperature sensor malfunction 1. Replace a normal one
2. Repair it or change a normal one
2. Circulating the water pump malfunction
3. Clean the water filter
03 Anti-freezing protection in cooling mode 3. The water filter clogging
Po 4. The evaporator tubes have a dirty plugging phenomenon 4. Clean the evaporator tubes
5. Refrigerant leak 5. Find out the leak point, repair the welding, refill
the unit after vacuuming it
1. The temperature sensor broken 1. Replace the sensor
06 The water outlet temperature is the fault 2. Sensor plug insert again to PCB 2. Reconnect the sensor firmly
Po 3. Main control board malfunction 3. Replace the main control board
07 Circulating the water anti-freezing protection in The outdoor ambient temperature is too low Start the heating mode
Po winter
Pr:02 Exchanger coil temperature sensor the fault of 1. Sensor is an open or short circuit 1. Replace the sensor
subsystem 1# 2. Sensor separated from the copper tube 2. Refix the sensor correctly
Pr:12 Exchanger coil temperature sensor the fault of 3. Sensor plug insert again 3. Reinsert firmly
subsystem 2# 4. Main control board malfunction 4. Replace the main control board
Pr:03 Discharge temperature sensor the fault of 1. Sensor is an open or short circuit 1. Replace the sensor
subsystem 1# 2. The sensor separates from the copper tube 2. Refix the sensor correctly
Pr:13 Discharge temperature sensor the fault of 3. Sensor plug insert again 3. Reinsert firmly
4. Main control board malfunction 4. Replace the main control board
subsystem 2#
1. The outdoor ventilation is insufficient 1. Improve or enhance the ventilation
Pr:04 Cooling overload protection of subsystem 2. The outdoor fan blade is broken 2. Replace the fan blade
1# 3. The connection between the fan blade and the outdoor fan 3. Tighten or replace the sleeve
motor lose
4. The outdoor fan stops working 4. Eliminate the malfunction cause
5. Exchanger coil bottom temperature sensor malfunction 5. Replace the sensor
Pr:14 Cooling overload protection of subsystem 6. The outdoor exchanger is dirty or sticky 6. Clean the heat exchanger
2# 7.  There are some airs in the refrigerant line 7. Refill the freon unit after vacuuming it
8. The capillary or the filter is blocked 8. Replace the capillary or filter

 

 

 